Toshiba Worldwide
Language selector
Japanese
Products & Services
Maintenance Items for Operating Time
Maintenance Points for Major Components
Site Search
Home
>
Thermal Power > Services & Maintenance
>
Generators & Electrical Systems
>
Inspection Services
We recommend generator maintenance as per below.
Operating Time 8~10years
Operation
Item
Part
Interval
Applied Cooling
Type
2 years
Inspection of High Voltage Bushing
Stator
Every 2years
All Types * Inapplicable in case of without Copper Bar
Fastening Bolts of Packing Gland
Stator
Every 2years
All Types
Maintenance and Inspection of generator Cooler, Including Cooler for Stator Winding Cooling System, Cooler for IPB
Auxiliaries
Every 2years
All Types
Inspection of AC Exciter & Auxiliaries
Auxiliaries
Every 2years
All Types* Applicable only DC Excitation System
4~6years
Overall Inspection for Field Endwinding
Rotor
Every 4 years
All Types
Overall Inspection for Stator Winding
Stator
Every 4 years
All Types
Inspection of Bushing Current Transformer
Auxiliaries
Every 4 years
All Types
Inspection of AC Exciter
Auxiliaries
Every 4 years
All Types* Applicable only DC Excitation System
Non-Destructive Examination of Rotor & Auxiliaries
Special Menu
Generator Retaining Rings Replacement
Rotor
Every 4~6years
All Types
8~10 years
(Special Examination) Capacitance Mapping Test for Water Cooled Stator Winding First time: 10 years after starting operation After: Every 2 years If check result is failure, we recommend rewinding
Special Menu
Capacitance Measuring Robot
Stator
Every 2years
Water cooled stator winding type only.
(Special) Inspection of High Voltage Bushing
Stator
Every 8 years
All Types* Inapplicable in case of without Copper Bar
(Special) Inspection of AC Exciter
Auxiliaries
Every 8 years
All Types* Applicable only DC Excitation System
(Special) Maintenance and Inspection of Generator Cooler, Including Cooler for Stator Winding Cooling System, Cooler for IPB at Site
Auxiliaries
Every 8~10 years
All Types
To Top
Site Map
|
Contact Us
|
Terms and Conditions
|
Privacy Policy